Western Innovator HBAC2 manifolds are designed and manufactured for high-purity gas delivery applications requiring uninterrupted gas flow and greater cylinder capacities. User friendly and easy to operate, a simple rotation of the control knob resets the unit. Factory-set functional components are protected inside a tamper-resistant case. A self-contained alarm system clearly indicates the system status. A green light means the system is ready for service. A red light alerts the user that the unit has changed over. Dry contacts in the unit's power supply box allow connection to remote alarms systems.
Unit of Measure
Specifications
Maximum Inlet Pressure |
N/A 3000 psig |
Maximum Flow Rate |
N/A 250 scfh |
Delivery Pressure Range |
N/A 30 to 100 psig |
Gas Service |
N/A Hydrogen CGA-350 |
Manifold Outlet Outside Diameter Tube Fitting Size |
N/A 1/4 in |
Header Size |
N/A 1/2 in |
Header Material |
N/A Brass |
Relief Valve Outlet Size |
N/A 1/2 in |
Relief Valve Outlet Thread Type |
N/A Female National Pipe Thread (FNPT) |
Helium Leak Rate Integrity |
N/A 2 x 10-6 scc/sec |
Number of Cylinders |
N/A 6 |
Header Configuration |
N/A Standard |
Mounting |
N/A Floor Mounted |
Overall Manifold Length |
N/A 5 ft. 7 in. 1.7 m |
Additional Information
Additional Information |
N/A
|